If the unit runs well in pool heating and A/C, trips on high pressure in dehumidifica tion, and runs higher than normal pressures in pool heat alone, then the A/C three-way valve is not shifting completely out of air conditioning. (This is assuming that no other cause for a high pressure trip can be found. If the unit runs fine in pool heating and/or A/C, trips on high pressure in dehumidification mode, and also runs with higher than normal pressures in A/C alone, then the pool heating three-way valve is not shifting completely out of pool heat. If no changes occur, then the valve is completely jammed and must be replaced. Force the suspect valve to operate and check for changes in operating temperatures and pressures. #Dectron dsv installation manual software#Download Free Software Last Chaos German Setup New Email. Verify that the three-way valve may be jammed: 1.ĭownload Game Football Manager Untuk Pc Ukuran Kecil.